Power distribution, with purpose.
Instrument transformers connect switchgear’s primary circuits to meters and protective relays, but selecting a current transformer (CT) is more than choosing a ratio. The ratio, connected burden, accuracy class, polarity, and physical arrangement must work together with the devices and protection scheme. A well-defined integration package gives the responsible engineer the information needed to confirm selections and settings before equipment is released for manufacture.
Start with the metering and protection requirements
The first input is a one-line diagram and a clear description of what each CT will serve. A revenue or operational meter, an overcurrent relay, a differential scheme, and a monitoring system may have different accuracy and performance needs, even when they share a switchgear lineup. Identify each device, its function, the phase or neutral connections required, and whether separate CT cores are specified for metering and protection. A shared core may be possible in some designs, but it can introduce competing requirements and should not be assumed suitable.
The responsible engineer should establish the system nominal voltage, equipment ratings, available fault current, grounding method, and protection philosophy. These details affect the application and coordination of instrument transformers, but they do not by themselves determine a CT selection. Provide the meter and relay manufacturer, model, input requirements, and applicable project specifications when available. Final ratios, accuracy classes, protection performance, and relay settings remain engineering decisions, not choices made from a catalog value alone.
Evaluate ratio, burden, and accuracy together
A CT ratio relates primary current to the current presented at its secondary terminals. The selected ratio should reflect expected operating conditions and the measurement or protection purpose, while considering how the connected device uses its input. A ratio that is too high for the normal load may reduce useful measurement resolution; one that does not suit the protection application may affect the engineer’s assessment of relay performance. Supply expected load current, growth assumptions, and the relevant fault or protection study information so the engineer can evaluate the tradeoff.
Burden is the load placed on a CT secondary by connected instruments, relays, leads, and terminal connections. Lead length and conductor size can matter, particularly when devices are remote from the switchgear. Accuracy class describes performance under defined conditions; it is not a blanket guarantee that a CT will meet every system need. The specified class and burden must be considered together with the CT design and the complete secondary circuit. Any proposed value should be checked against the device data and project criteria before it is accepted.

Coordinate cores, polarity, and secondary interfaces
Where a CT has multiple cores or secondary windings, assign each one to a documented purpose. Separate metering and protection cores can help avoid conflicts, but core count, ratios, terminals, and available physical space depend on the specific design. The drawings should identify primary polarity, secondary polarity, terminal markings, phase designations, and the intended destination of each circuit. Those conventions must align with the one-line, elementary diagrams, and relay or meter wiring information so that design, manufacturing, testing, and field review use consistent references.
The integration review also needs to address how CT secondary wiring leaves the assembly and interfaces with customer-supplied devices or external control wiring. Confirm terminal locations, wiring and cable expectations, shorting provisions where applicable, and the division of responsibility for interconnection. CT secondary circuits require particular care: an open secondary while primary current is flowing can create a hazardous voltage. Design documentation should make the intended circuit arrangement clear, while work practices and commissioning remain subject to qualified personnel and the project’s safety procedures.
Define the physical arrangement and design records
For a quotation, provide the equipment configuration and drawings needed to assess CT fit and interfaces, including the one-line, lineup or compartment arrangement, bus details where available, and any dimensional or access constraints. Also identify the intended instrument transformers, meters, relays, and customer-furnished components, or state which selections are still pending engineering review. Incomplete inputs can lead to assumptions about space, conductor routing, terminal access, or device connections that later require resolution before release.
A planned integration drawing package can document CT identification, ratio and core assignments, polarity, terminal references, secondary wiring destinations, and interfaces to the meter and relay circuits. Depending on the agreed scope, related records may include connection diagrams, bills of material, and engineering review comments. These deliverables should distinguish confirmed project data from assumptions and open items. The manufacturer’s role, the purchaser’s responsibilities, and the responsible engineer’s approval points should be stated in the quote and submittal process rather than inferred from a drawing title.
Set scope boundaries and confirm project-specific requirements
Instrument transformer integration can be considered as part of a new switchgear build, subject to review of the requested configuration and available components. It should not be represented as a substitute for a protection study, meter programming, relay settings, system commissioning, or approval by the engineer of record. Unless specifically confirmed in the proposal, do not assume that the scope includes those services, field installation, testing at the customer site, or coordination with utility requirements. Each of these responsibilities should be assigned explicitly before an order is finalized.
For Dallas–Fort Worth projects and shipments elsewhere in the United States, the same technical inputs are needed: project drawings, device data, system conditions, governing specifications, and a defined scope. Ratings, short-circuit capability, component availability, applicable standards, and any U.S.-origin requirements must be confirmed for the specific order. UL 891 may apply to qualifying low-voltage switchboard assemblies; it is not a general listing for medium-voltage switchgear or instrument transformers. Submit the applicable project requirements with the quotation request so feasibility, documentation, and any outstanding engineering decisions can be reviewed without treating an unverified capability as a commitment.
Specifications & planning
Review the details that matter for your application. Final specifications and availability should be confirmed for your project.
| Evaluation factor | Information to confirm |
|---|---|
| CT ratio | Expected load, measurement range, and protection application; final selection by responsible engineer |
| Burden | Connected device data, lead length, conductor details, and secondary circuit arrangement |
| Accuracy and cores | Required function, accuracy criteria, core assignments, and applicable CT documentation |
| Integration records | Drawing scope, polarity and terminal references, interfaces, and approval responsibilities |