NEW AMERICAN-MADE POWER DISTRIBUTIONSERVING DALLAS – FORT WORTH
Switchgear cabinets arranged on a warehouse floor
NEW EQUIPMENT FOR DALLAS–FORT WORTH

25 kV Class Switchgear Specification Guide

Plan 25 kV-class switchgear around system grounding, equipment ratings, insulation, protection, and service interfaces before requesting a quote.

MADE IN USAAmerican components
UL 891Switchboard assemblies
SHORT LEAD TIMESConfirm your project schedule
BUILT FOR YOUR PROJECT

Power distribution, with purpose.

A 25 kV class designation identifies a medium-voltage equipment category, not a complete statement of what a particular system requires or what a manufacturer offers. Start with the system’s nominal voltage, grounding method, fault conditions, and operating environment; then confirm the equipment’s applicable ratings and configuration for the order.

Separate the system voltage from the equipment rating

Specify the system’s nominal line-to-line voltage and the highest voltage expected under normal operating conditions. A 25 kV class is commonly associated with systems in the 20–25 kV range, but the class name alone does not establish the equipment’s maximum rated voltage. That value must suit the actual system and applicable design requirements; do not substitute a nominal system voltage for an equipment rating.

Where the source or load is described line-to-neutral, provide that value alongside the line-to-line voltage and explain how the system is connected. For a grounded three-phase system, line-to-neutral voltage is related to line-to-line voltage, but that relationship does not by itself define insulation requirements or fault behavior. A single-line diagram and grounding details help avoid mismatched assumptions when reviewing the proposed configuration.

Document grounding and fault conditions

Grounding affects phase-to-ground stress, ground-fault current, protective-device operation, and the way a fault is detected and cleared. Identify whether the system is solidly grounded, resistance grounded, reactance grounded, or otherwise configured, and state relevant grounding-transformer or neutral arrangements. If the design changes operating modes, such as when a source is disconnected or a tie is closed, describe each mode that could alter ground-fault conditions.

Provide available fault-current information at the switchgear connection, including the study basis and any credible operating configurations. The specified short-circuit rating, interrupting devices, and protection coordination must be appropriate to those conditions and the selected components. A 25 kV class label does not establish a short-circuit capability. Ask the manufacturer to review the project data and confirm the ratings and component availability for the specific proposed build.

Illustrative close-up of copper busbars in a motor control panel
Illustrative industry photograph · ToT89 / Wikimedia Commons · resized · CC BY-SA 4.0

Match insulation requirements to the installation

Insulation coordination is more than selecting a voltage class. The specification should identify the applicable equipment insulation levels and withstand requirements, along with exposure to switching surges, lightning surges, and grounding conditions where relevant. State whether surge arresters or other protective devices are part of the intended system design, and clarify who is responsible for selecting and coordinating them. Confirm the exact requirements against the governing project documents and standards rather than relying on a class name as a substitute.

Installation conditions can influence the design review. Provide indoor or outdoor location, elevation, ambient temperature range, humidity or contamination concerns, enclosure requirements, and any unusual ventilation or space constraints. Also identify cable entry direction, termination type, conductor arrangement, and clearances at the interface. These details matter for fit and coordination; they should be checked before an order is finalized, not inferred from a generic 25 kV description.

Coordinate frequency, protection, and operating interfaces

State the system frequency and identify how the switchgear will connect to upstream and downstream equipment, including transformers, utility or generator sources, bus ties, and major loads. Specify the intended protection functions and relay or control interfaces where they are defined by the project. Relay settings and coordination should follow the protection study and be reviewed by the responsible engineering parties; equipment selection alone does not establish a complete protection scheme.

Describe the operating sequence and interlocks needed at the system level, including any transfer or tie operation that affects source configuration. Identify control-power requirements, remote indication or communications interfaces, and any requirements for metering or instrument transformers. Clarifying responsibility for these interfaces reduces the risk of gaps between switchgear, relays, cables, and adjacent equipment. Do not assume that a feature or specific component is available in a proposed build until it has been confirmed for that configuration.

Prepare a project-specific request for quotation

For a useful quotation review, supply the single-line diagram, nominal system voltage, frequency, grounding description, available fault-current study, and the requested equipment and insulation ratings. Include the protection and control scope, incoming and outgoing cable details, bus or tie arrangement, installation environment, applicable standards, and required documentation. State the delivery destination and schedule needs as planning inputs, without treating a requested date as a guaranteed lead time.

A manufacturer serving Dallas–Fort Worth and shipping nationwide can review a new custom-built equipment request, but the specific 25 kV class configuration must be validated before anyone makes a product claim. Request confirmation of offered scope, component availability, ratings, applicable standards, and any U.S.-origin requirements for the order. UL 891 applies to low-voltage switchboards, not as a general listing for 25 kV class medium-voltage switchgear. Shorter lead time may be a goal, but timing depends on the confirmed design and supply conditions.

PROJECT CONSIDERATIONS

Specifications & planning

Review the details that matter for your application. Final specifications and availability should be confirmed for your project.

25 kV Class voltage planning: specifications and planning considerations
Evaluation factorInformation to confirm
System voltageNominal line-to-line and, where applicable, line-to-neutral values
Grounding and faultsGrounding method, operating modes, and available fault-current study
Equipment insulationRequired rating and withstand levels, subject to engineering review
Installation interfacesEnvironment, cable terminations, controls, and adjacent equipment
READY TO DISCUSS YOUR PROJECT?Let's build what's next.
Call (951) 403-5738
LET'S GET TO WORK

Power your next project
with confidence.

Talk through your switchgear and power distribution needs with our team.

Call (951) 403-5738
Request a Quote